Insulated parts of Live Line Tools shall have manufacturers' certification to withstand the following minimum tests:
(1) 100,000 volts per foot of length for five minutes when the tool is made of fiberglass; or
(2) 75,000 volts per foot of length for three minutes when the tool is made of wood; or
(3) other tests equivalent to (1) or (2) above as appropriate.