This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
Article 36. Work Procedures and Operating Procedures (Formerly Article 85)
Return to index
New query

§2940.9. Protection from Backfeed Voltages.


Before contacting the high voltage side of deenergized transformer(s), or conductor(s) connected thereto, all possible sources of backfeed shall be eliminated by:

(a) disconnecting or grounding the high voltage side, or

(b) disconnecting or short circuiting the low voltage side.

EXCEPTION: System(s) worked as energized.

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.