This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 7. General Industry Safety Orders
Group 20. Flammable Liquids, Gases and Vapors
Article 147. Bulk Plants

Return to index
New query


§5617. Buildings.


(a) Rooms in which flammable or combustible liquids are stored or handled by pumps, shall have exit facilities arranged to prevent occupants being trapped in the event of fire.
(b) Rooms in which Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100oF (37.8oC) are stored or handled shall be heated only by means not constituting a source of ignition, such as steam or hot water. Rooms containing heating appliances involving sources of ignition shall be located and arranged to prevent entry of flammable vapors.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.