This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 7. General Industry Safety Orders
Group 20. Flammable Liquids, Gases and Vapors
Article 145. Tank Storage

Return to index
New query


§5585.1. Liquid Level Indicator, Temperature Regulator, Class IIIB.


Atmospheric tanks used for storing combustible liquids (as defined in Section 5415) heated by internal heating coil/element shall be equipped with a liquid level indicator or equivalent device that displays the liquid level in the tank; or a temperature regulating system. When equipped with a temperature regulating system, the temperature regulating system shall automatically shut off the heat source to the tank before the tank contents reach the ignition temperature. If a liquid level indicator is the sole sensing method, 1) the liquid level indicator shall be affixed to the tank or located elsewhere, such as in a control room, 2) the liquid level indicator shall be monitored when filling or emptying the tank, 3) the location of the internal heating coil/element on the tank shall be clearly indicated.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
HISTORY
1. New section filed 1-16-96; operative 2-15-96 (Register 96, No. 3).
2. Amendment of section heading and section filed 5-5-2014; operative 5-6-2014 pursuant to Government Code section 11343.4(b)(3) (Register 2014, No. 19).

Go BackGo Back to Article 145 Table of Contents