ยง5535. Storage in Inside Storage Rooms.
In every inside storage room there shall be maintained one clear aisle at least three feet wide. Containers over 30 gallons capacity storing Category 1, 2 or 3 flammable liquids shall not be stacked one upon the other. Dispensing shall be by approved pump or self-closing faucet only.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
HISTORY
1. Amendment filed 7-16-76; effective thirtieth day thereafter (Register 76, No. 29).
2. Amendment of section and new Note filed 5-5-2014; operative 5-6-2014 pursuant to Government Code section 11343.4(b)(3) (Register 2014, No. 19).