This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 7. General Industry Safety Orders
Group 18. Explosives and Pyrotechnics
Article 122. Ammonium Nitrate Storage
Return to index
New query

§5362. Container Storage.




(a) Bags and containers used for ammonium nitrate shall comply with specifications and standards required for use in interstate commerce.

(b) Containers of ammonium nitrate shall not be accepted for storage when the temperature of the ammonium nitrate exceeds 130o F.



Exception: Containers used on the premises in the manufacturing or processing need not comply with the provisions of subsections (a) or (b).

(c) Bags of ammonium nitrate shall not be stored within 30 inches of the storage building walls and partitions.

(d) The height of stacked bags shall not exceed 20 feet. The width of the stacked bags shall not exceed 20 feet and the length 50 feet except that where the building is of noncombustible construction or is protected by automatic sprinklers the length of piles shall not be limited. In no case shall the ammonium nitrate be stacked closer than 36 inches below the roof or supporting and spreader beams overhead.

(e) Aisles shall be provided to separate piles by a clear space of not less than 3 feet in width. At least one service or main aisle in the storage area shall be not less than 4 feet in width.

NOTE

Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

HISTORY

1. Amendment of subsections (a), (b) and (d) and new Note filed 7-11-2003; operative 8-10-2003 (Register 2003, No. 28).

Go BackGo Back to Article 122 Table of Contents