Skip to Main Content


This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 6. Elevator Safety Orders
Article 15. Special Access Lifts
Return to index
New query

§3093.52. Suspension Ropes.


(a) On elevators having a rated load of 450 lb. (204 kg) or less and operating at a rated speed of 30 fpm (0.15 m/s) or less, suspension ropes shall be not less than 1/4 in. (6.3 mm) in diameter.

(b) On elevators having a rated load of more than 450 lb. and less than 750 lb. and operating at a rated speed of 30 fpm or less, suspension ropes shall be not less than 3/8 in. in diameter.

(c) Where the rated load is more than 750 lb. or the rated speed exceeds 30 fpm, each suspension rope shall have a safety factor of not less than 7.5.

(Title 24, Part 7, Section 7-3093.52)

NOTE

Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

HISTORY

1. New section filed 7-22-86; effective thirtieth day thereafter (Register 86, No. 36).

2. Amendment of section heading and section filed 8-29-2001; operative 9-28-2001 (Register 2001, No. 35).

Go BackGo Back to Article 15 Table of Contents