This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
Article 33. Mine and Tunnel Installations (Formerly Article 82)
Return to index
New query

§2917. Bonding and Equipment Grounding Conductor.


(a) All non-energized metal parts of electrical equipment and all metal raceways or cable sheaths shall be effectively grounded and bonded to all metal pipes and rails at the portal and at intervals not exceeding 1,000 feet throughout the tunnel.

(b) An equipment grounding conductor shall be run with circuit conductors inside the metal raceway or inside the multi-conductor cable jacket. The equipment grounding conductor shall be permitted to be insulated or bare.

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.