This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
ARTICLE 20. INTERRUPTING AND ISOLATING DEVICES
Return to index
New query

§2850. Interrupting Rating.


The interrupting rating of oil-filled cutouts shall equal or exceed the maximum fault current available at the cutout location, including contributions from all connected sources of energy, such as other lines, generators, large motors, etc.

(Title 24, Part 3, Section 710-21(d)(2).)

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 189243(c), Health and Safety Code.

HISTORY

1. Editorial correction adding NOTE filed 11-2-83 (Register 83, No. 45).

2. Amendment filed 12-10-87; operative 1-9-88 (Register 88, No. 1).