This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
Article 11. Metal-Enclosed Bus (Formerly Article 60)
Return to index
New query

§2770. Switches.


Switching devices or disconnecting links provided in the bus run shall have the same momentary rating as the bus.

Disconnecting links shall be plainly marked to be removable only when bus is de-energized. Switching devices which are not load break shall be interlocked to prevent operation under load and disconnecting link enclosures shall be interlocked to prevent access to energized parts.

(Title 24, Part 3, Section 364-29.)