Overhead or underground services or service entrance conductors shall not supply one building through another.
EXCEPTION: This requirement does not apply to conductors in conduit or duct placed under or encased in at least 3 inches of concrete or equivalent fire-resistant material.
(Title 24, Part 3, Section 3-230-202(i).)
NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.