This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 1. Low-Voltage Electrical Safety Orders
Article 74. Cranes and Hoists
Return to index
New query

§2561.3. Clearance.


(a) On every new installation, major replacement, modification or repair made after March 15, 1972, the dimension of the working space in the direction of access to energized parts which may require examination, adjustment, servicing, or maintenance while energized shall be a minimum of 2.5 feet (762 mm). Where controls are enclosed in cabinets, the doors shall either open at least 90 degrees or be removable.

Note: For the purpose of this section, a major replacement, modification, or repair shall mean 50 percent or more of the current replacement value of the crane or hoist.

(b) On floor operated overhead cranes a suitable work platform with means of access shall be provided, attached to the building structure, or on the overhead crane bridge, giving ready and safe access to electrical control cabinets for service, maintenance or repair.

Exception: Floor operated porta-lift type platforms, rolling scaffolds or similar type platforms may be used.

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.