This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 6. Elevator Safety Orders
Article 12.3. Special Purpose Personnel Elevators
Return to index
New query

§3085.12. Car and Counterweight Buffers [Rule 1502.2].


(a) Car and counterweight buffers shall be provided and shall conform to the applicable requirements of Section 3031.

(b) For rack and pinion elevators, spring buffers, where used, shall be so designed and installed that they will not be fully compressed when struck by the car with its rated load at governor tripping speed where the safety is governor operated, or at 125% of rated speed where the safety is not governor operated. Kinetic energy from the drive unit shall be taken into account in the design calculations. The effect of the counterweight, where used, may also be taken into account in the design calculations.

(Title 24, Part 7, Section 7-3085.12)

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.