This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
Article 39. Signs and Outline Lighting--Exceeding 600 Volts (Formerly Article 88)
Return to index
New query

§2973. Terminals and Electrode Receptacles for Electric-Discharge Tubing.


Terminals and electrode receptacles for electric-discharge tubing shall comply with the following:

(a) Terminals. Terminals of the tubing shall be inaccessible to unqualified persons and isolated from combustible material and grounded metal or shall be enclosed.

(Title 24, Part 3, Section600-34(a).)

(b) Tube Connections. Where tubes do not terminate in receptacles designed for the purpose, all live parts of tube terminals and conductors shall be so supported as to maintain a separation of at least 1 1/2 inches between conductors or between conductors and any grounded metal.

(Title 24, Part 3, Section 600-34(b).)

(c) Bushings. Where electrodes enter the enclosure of outdoor signs or of an indoor sign operating at a voltage in excess of 7.5 kilovolts, bushings shall be used unless receptacles are provided or the sign is wired with bare wire mounted on approved supports which maintain the tubing in proper position.

(Title 24, Part 3, Section 600-34(d).)

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.