This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
Article 32. Mobile and Portable Equipment (Formerly Article 81)
Return to index
New query

§2907. Overcurrent Protection.


Motors driving single or multiple d.c. generators supplying a system operating on a cyclic load basis do not require running overcurrent protection, provided that the thermal rating of the a.c. drive motor cannot be exceeded under any operating condition. However, the branch circuit protective device(s), which may be external to the motor, must provide short circuit and locked rotor protection.

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

HISTORY

1. Editorial correction adding NOTE filed 11-2-83 (Register 83, No. 45).