This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
Article 15. Temporary Wiring
Return to index
New query

§2799.2. Branch Circuits.



The following requirements apply to branch circuits:

(a) Branch circuits shall originate in an approved panelboard.

(b) Conductors shall be multiconductor cord or cable assemblies or open conductors.

(c) No branch-circuit conductor may be laid on the floor.

(d) Each branch circuit that supplies fixed equipment shall contain a separate equipment grounding conductor if run as open conductors.

<General Materials (GM) - References, Annotations, or Tables>


   Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code