Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
Article 5. Feeders and Branch Circuits
§2738. Identification of Multiwire Branch Circuits.
Where more than one nominal voltage system exists in a building containing multiwire branch circuits, each ungrounded conductor of a multiwire branch circuit, where accessible, shall be identified by phase and system. The means of identification shall be permanently posted at each branch-circuit panelboard.
<General Materials (GM) - References, Annotations, or Tables>
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.