This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 1. Low-Voltage Electrical Safety Orders
Article 77. Data Processing Systems
Return to index
New query

§2565.3. Disconnecting Means.


(a) A disconnecting means shall be provided to disconnect the power to all electronic equipment in an information technology equipment room. There shall also be a similar means to disconnect the power to all dedicated heating, ventilating and air conditioning (HVAC) systems serving the room and to cause all required fire/smoke dampers to close.

Exception: Integrated electrical systems covered by Article 89 need not have the disconnecting means required by this section.

(b) Grouping. The control for these disconnecting means shall be grouped and identified and shall be readily accessible at the principal exit doors. A single means to control both the electronic equipment and HVAC system is permitted.

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.