This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 1. Low-Voltage Electrical Safety Orders
Article 56. Motors, Motor Circuits and Controllers

Return to index
New query


§2530.86. Motor Not in Sight from Controller.

Lockout/Blockout Methods and Sample Procedures
(a) If a motor and the driven machinery are not in sight from the controller location, the installation shall comply with one of the following conditions:
(1) The controller disconnecting means shall be capable of being locked in the open position.
(2) A manually operable switch that will disconnect the motor from its source of supply shall be placed in sight from the motor location.
(Title 24, Part 3, Section 430-86.)