(a) Unless specifically permitted otherwise in Section 2500.7, flexible cords and cables shall not be used:
(1) as a substitute for the fixed wiring of a structure;
(2) where run through holes in walls, ceilings, or floors;
(3) where run through doorways, windows or similar openings;
(4) where attached to building surfaces;
(5) where concealed behind building walls, ceilings, or floors; or
(6) Where installed in raceways, except as otherwise permitted in these Electrical Safety Orders.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.