(a) Metal cable trays, metal raceways, and metal enclosures for conductors shall be grounded, except that:
(1) Metal enclosures such as sleeves that are used to protect cable assemblies from physical damage need not be grounded; and
(2) Metal enclosures for conductors added to existing installations of open wire, knob-and-tube wiring, and nonmetallic-sheathed cable need not be grounded if all of the following conditions are met:
(A) Runs are less than 25.0 feet (7.62 meters);
(B) Enclosures are free from probable contact with ground, grounded metal, metal laths, or other conductive materials; and
(C) Enclosures are guarded against employee contact.
(b) Metal enclosures for service equipment shall be grounded.
(c) Frames of electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, and metal outlet or junction boxes that are part of the circuit for these appliances shall be grounded.