Skip to Main Content


This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 7. General Industry Safety Orders
Group 20. Flammable Liquids, Gases and Vapors
Article 143. Processing Plants

Return to index
New query


§5556. Construction.


(a) Processing buildings shall be of not less than noncombustible construction, except heavy timber construction with load-bearing walls may be permitted for plants utilizing only stable Category 3 flammable liquids with a flashpoint at or above 100oF (37.8oC) or Category 4 flammable liquids including liquids with a flashpoint greater than 199.4oF (93oC) (formerly designated Class IIIB Combustible liquids). Except as provided in Section 5555(b) or in the case of explosion resistant walls used in conjunction with explosion relieving facilities, see (f), load-bearing walls shall be prohibited. Buildings shall be without basements or covered pits.
(b) Areas shall have adequate exit facilities arranged to prevent occupants from being trapped in the event of fire (see Article 2).
(c) Exits shall not be exposed by the drainage facilities described in Section 5546(a) and (b).
(d) Enclosed processing buildings handling Category 1, 2 or 3 flammable liquids shall be ventilated at a rate of not less than one cubic foot per minute per square foot of solid floor area. This shall be accomplished by natural or mechanical ventilation with discharge or exhaust to a safe location outside of the building. Provision shall be made for introduction of make-up air in such a manner as not to short circuit the ventilation. Ventilation shall be arranged to include all floor areas or pits where flammable vapors may collect. Local (or spot) ventilation may be needed for the control of special fire or health hazards. Such ventilation, if provided, may be utilized for up to 75 percent of the required ventilation.
(e) Equipment used in a building and the ventilation of the building shall be designed so as to limit flammable vapor-air mixtures under normal operating conditions to the interior of equipment, and to not more than five feet from equipment which exposes Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100oF (37.8oC), to the air. Examples of such equipment are dispensing stations, open centrifuges, plate and frame filters, open vacuum filters, and surfaces of open equipment.
(f) Areas where Category 1 or unstable liquids are processed shall have explosion venting through one or more of the following methods:
(1) Open air construction;
(2) Lightweight walls and roof;
(3) Lightweight wall panels and roof hatches;
(4) Windows of explosion venting-type.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
HISTORY
1. Amendment filed 7-16-76; effective thirtieth day thereafter (Register 76, No. 29).
2. Amendment of subsections (a), (d), (e) and (f) and new Note filed 5-5-2014; operative 5-6-2014 pursuant to Government Code section 11343.4(b)(3) (Register 2014, No. 19).

Go BackGo Back to Article 143 Table of Contents