Before contacting the high voltage side of deenergized transformer(s), or conductor(s) connected thereto, all possible sources of backfeed shall be eliminated by:
(a) disconnecting or grounding the high voltage side, or
(b) disconnecting or short circuiting the low voltage side.
EXCEPTION: System(s) worked as energized.
NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.