Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
Article 35. Workspace and Guarding (Formerly Article 84)

New query

§2934. Elevation of Unguarded Live Parts.

Exposed energized parts above workspace and above areas where persons may normally walk or stand shall be maintained at elevations not less than that required by the following table:


 
     VOLTAGE BETWEEN 
         PHASES                       ELEVATION 
        601-7500                   8 feet 6 inches 
      7501-35,000                      9 feet 
       over 35kv                9 feet + 0.37 inch/kv 
                                     above 35kv 

(Title 24, Part 3, Section 110-34(e).)

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.