This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
Article 26. Metal-Enclosed Power Switchgear and Industrial Control Assemblies (Formerly Article 75)
Return to index
New query

§2871. Interlocks--Circuit Breakers.


(a) Circuit breakers equipped with stored energy mechanisms shall be designed to prevent the release of the stored energy unless the mechanism has been fully charged.

(b) Mechanical interlocks shall be provided in the housing to prevent the complete withdrawal of the circuit breaker from the housing when the stored energy mechanism is in the fully charged position. In lieu of the above interlock, a suitable device may be provided which prevents the complete withdrawal of the circuit breaker until the closing function is blocked.

(Title 24, Part 3, Section 710-24(p).)

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.