This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
Article 26. Metal-Enclosed Power Switchgear and Industrial Control Assemblies (Formerly Article 75)
Return to index
New query

§2866. Door Stops and Cover Plates.


External hinged doors or covers for outdoor equipment shall be provided with stops to hold them in the open position. Cover plates intended to be removed for inspection of energized parts or wiring shall be locked or secured by other approved means and equipped with lifting handles and shall not exceed 12 square feet in area or 60 pounds in weight. If they exceed 12 square feet in area or 60 pounds in weight, they shall be hinged and bolted or locked.

(Title 24, Part 3, Section 710-24(i).)

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.