Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
Article 12. Continuous Rigid Cable Supports (Formerly Article 61)

New query

§2778. Grounding.

All metal sections of continuous rigid cable supports and fittings shall be electrically continuous and effectively grounded to provide a continuous circuit for fault current. A continuous rigid cable support system shall not be used either as a grounded circuit conductor or as an equipment grounding conductor.

(Title 24, Part 3, Section 3-318-6.)

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.