This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
Article 4. Service and Service Entrance Equipment (Formerly Article 53)
Return to index
New query

§2732. Paralleling and Isolating Switches.


(a) Two or more sets of service entrance conductors which can be operated in parallel shall be provided with a suitable means to isolate each set from all other sets of service entrance conductors.

(b) The paralleling switch or switches intended to make and break parallel shall conform to Article 20 or 21.

(c) Operation of paralleling switches shall be restricted to qualified and authorized persons only. A written switching procedure shall be made available to and followed by such personnel.

(Title 24, Part 3, Section 3-230-216.)

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.