This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 1. Low-Voltage Electrical Safety Orders
Article 83. Electrolytic Cells
Return to index
New query

§2583.6. Fixed and Portable Electric Equipment.


(a) The following need not be grounded:

(1) AC systems supplying fixed and portable electric equipment within the cell line working zone; and

(2) Exposed conductive surfaces, such as electric equipment housings, cabinets, boxes, motors, raceways and the like that are within the cell line working zone.

(b) Auxiliary electric equipment, such as motors, transducers, sensors, control devices, and alarms, mounted on an electrolytic cell or other energized surface shall be connected to the premises wiring systems by any of the following means:

(1) Multiconductor hard usage or extra hard usage flexible cord;

(2) Wire or cable in suitable nonmetallic raceways or cable trays; or

(3) Wire or cable in suitable metal raceways or metal cable trays installed with insulating breaks such that they will not cause a potentially hazardous electrical condition.

(c) Fixed electric equipment may be bonded to the energized conductive surfaces of the cell line, its attachments, or auxiliaries. If fixed electric equipment is mounted on an energized conductive surface, it shall be bonded to that surface.

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.