| This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at http://www.dir.ca.gov/od_pub/disclaimer.html. |
| Return to index New query |
(a) Vertical and Horizontal. Signs and outline system enclosures shall have not less than the vertical and horizontal clearances from open conductors specified in the following table:
TABLE 2560.10
CLEARANCES
Vertical clearance above all signs upon which persons can walk..... 8 feet
Vertical clearance above all signs upon which persons cannot walk.. 3 feet
Vertical clearance under signs..................................... 3 feet
Horizontal clearance from signs.................................... 3 feet
(Title 24, Part 3, Section 3-600-10(a).)
(b) Elevation. The bottom of sign and outline lighting enclosures shall not be less than 16 feet above areas accessible to vehicles.
EXCEPTION: The bottom of such enclosures may be less than 16 feet above areas accessible to vehicles where such enclosures are protected from physical damage.
(Title 24, Part 3, Section 600-10(b).)