This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 1. Low-Voltage Electrical Safety Orders
Article 59. Hazardous (Classified) Locations
Return to index
New query

§2540.10. Wastewater Wells.


(a) Definition.

(1) Sewage Wastewater Well (wet or dry types): A physical structure, usually underground, the prime function of which is to lift wastewater.

(2) Sewage Drywell: A sewage well which does not incorporate a reservoir in addition to the pump(s).

(3) Sewage Wetwell: A sewage well which incorporates a reservoir in addition to the pump(s).

(Title 24, Part 3, Section 3-512-9.)

(b) Hazardous Locations. Sewage wells, and the surrounding enclosure shall be classified in accordance with Section 2540.1 and the following:

(1) Sewage Dry Well. The interior of sewage dry wells shall be classified as a Class I, Division 2 location.

EXCEPTION: A sewage dry well shall be permitted to be unclassified provided the following conditions are met:

(A) The well and the surrounding enclosure is treated in accordance with the provisions of the General Industry Safety Orders, Article 108, as a potential confined space; and

(B) The well and surrounding area are provided with a suitable, continuously operating ventilation system to maintain the flammability of the interior atmosphere below 20% of the lower explosive limit (LEL). The air for the ventilation systems shall be supplied from a non-hazardous source. Means shall be provided to automatically de-energize all electrical sources of ignition in the well in the event of ventilation system failure, which would result in the interior atmosphere of the well reading 20% of the lower explosive limit (LEL).

(2) Sewage Wet Well. The interior of sewage wet wells shall be classified as a Class I, Division 1, location.

EXCEPTION: No. 1: A sewage wet well shall be permitted to be classified as Class I, Division 2, location provided the following conditions are met:

(A) The well and surrounding area are treated in accordance with the provisions of the General Industry Safety Orders, Article 108, as a potential confined space; and

(B) The well and surrounding area are provided with a suitable, continuously operating ventilation system to maintain the flammability of the interior atmosphere below 20% of the lower explosive limit (LEL). The air for the ventilation system shall be supplied from a non-hazardous source. Means shall be provided to automatically de-energize all electrical sources of ignition in the well in the event of ventilation system failure, which would result in the interior atmosphere of the well reaching 20% of the lower explosive limit (LEL).

EXCEPTION: No. 2: A sewage wet well shall be permitted to be classified as a Class I, Division 2, location provided the following conditions are met:

(A) The well and surrounding area are treated in accordance with the provisions of the General Industry Safety Orders, Article 108, as a confined space, and

(B) The pump motor(s) is completely submerged in the water whenever the motor is running, and

(C) The motor controller(s) is identified for use in a Class I location or is located outside the classified location, and

(D) The sensors-transducers are identified as intrinsically safe or for use in a Class I location.

(Title 24, Part 3, Section 3-521-10.)

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.