This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 1. Low-Voltage Electrical Safety Orders
Article 48.1. Enclosures for Damp or Wet Locations
Return to index
New query

§2485.1. Cabinets, Cutout Boxes, Fittings, Boxes, and Panelboard Enclosures.


(a) Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations shall be installed so as to prevent moisture or water from entering and accumulating within the enclosures and shall be mounted so there is at least 0.25 in. (6.35 mm) airspace between the enclosure and the wall or other supporting surface.

Exception: Nonmetallic enclosures may be installed without the airspace on a concrete, masonry, tile, or similar surface.

(b) Enclosures shall be weatherproof in wet locations.

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.