This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 7. General Industry Safety Orders
Group 20. Flammable Liquids, Gases and Vapors
Article 145. Tank Storage

Return to index
New query


§5605. Protection of Tanks in Locations That May Be Flooded.


Where an underground or above ground storage tank installed on or after October 1, 2014, is located in an area that may be subjected to flooding as defined by the Federal Emergency Management Agency (FEMA), installation shall conform to NFPA 30: Flammable and Combustible Liquids Code, 2012 Edition (NFPA 30-2012), Chapter 21, Section 21.7.3, Chapter 22, Sections 22.5.2.5 and 22.14, Chapter 23, Section 23.14, and Annex A.23.14.1, which are hereby incorporated by reference. Such tanks in areas subject to flooding as defined by FEMA, installed prior to October 1, 2014, shall conform to either the foregoing provisions of NFPA 30-2012 or to NFPA 30: Flammable and Combustible Liquids Code, 1973 Edition (NFPA 30-1973), Appendix B, which is hereby incorporated by reference.
NOTE: FEMA flood maps and flood zone definitions are found at https://msc.fema.gov.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.