This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 7. General Industry Safety Orders
Group 20. Flammable Liquids, Gases and Vapors
Article 136. Dip Tanks
Return to index
New query

§5427. Ventilation.


(a) Vapor areas shall be limited to the smallest practical space by maintaining a properly designed system of mechanical ventilation arranged to move air from all directions towards the vapor origin area to a safe outside location. Ventilating systems shall conform to Section 5154.

(b) Required ventilating systems shall be so arranged that the failure of any ventilating fan shall automatically stop any dipping conveyor system.

(c) When a required ventilating system serves associated drying operations utilizing a heating system which may be a source of ignition, means shall be provided for pre-ventilation before heating system can be started; the failure of any ventilating fan shall automatically shut down the heating system; and the installation shall otherwise conform to NFPA Standard for Ovens and Furnaces (NFPA No. 86A1977).

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.