| This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at http://www.dir.ca.gov/od_pub/disclaimer.html. |
| Return to index New query |
(a) Protection Against Corrosion. Raceways and equipment, unless constructed of corrosion-resistant material, shall be suitably protected against corrosion inside and outside (except threads at joints).
(Title 24, Part 3, Section 300-6.)
(b) Secured in Place. Raceways shall enter and be secured to pull boxes, terminal enclosures and to cases, shields or enclosures of apparatus, except in vaults, substations or the space under high-voltage switchboards. Raceways shall be securely supported.
(Title 24, Part 3, Section 300-11.)
(c) Protection Against Weather. Raceways exposed to the weather shall be weatherproof.
(Title 24, Part 3, Section 110-11.)