This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 2. High-Voltage Electrical Safety Orders
Article 13. Metal-Clad Cable (Formerly Article 62)
Return to index
New query

§2783. Supports.


Metal-clad cable shall be permitted to be installed on metal racks, trays, troughs, or continuous rigid cable supports which are effectively grounded. Each cable shall be supported at intervals not exceeding 6 feet and within 2 feet of every box or fitting, and each cable shall be attached to the support at intervals of not more than 10 feet horizontally and 2 feet vertically.

(Title 24, Part 3, Section 3-334-25.)

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.