This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 1. Low-Voltage Electrical Safety Orders
Article 11. Grounding
Return to index
New query

§2395.79. Equipment Bonding Jumpers.


(a) Material. Equipment bonding jumpers shall be of copper or other corrosion-resistant material.

(b) Attachment. Equipment bonding jumpers shall be attached in the manner specified by the applicable provisions of Section 2395.113 for circuits and equipment.

(c) Installation. The equipment bonding jumper shall be permitted to be installed inside or outside of a raceway or enclosure. Where installed on the outside, the length of the equipment bonding jumper shall not exceed six (6) feet and shall be routed with the raceway or enclosure.

(Title 24, Part 3, Section 250-79(a), (b) and (e).)

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.