This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at http://www.dir.ca.gov/od_pub/disclaimer.html.

Subchapter 4. Construction Safety Orders
Article 15. Cranes and Derricks in Construction

Return to index
New query

§ 1612.2. Power Line Safety (Over 350 kV).

The requirements of Section 1611.5 and Section 1612.1 apply to power lines over 350 kV except:

(a) For power lines at or below 1000 kV, wherever the distance “20 feet” is specified, the distance “50 feet” shall be substituted; and

(b) For power lines over 1000 kV, the minimum clearance distance shall be established by the utility owner/operator or registered professional engineer who is a qualified person with respect to electrical power transmission and distribution.

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.