This information is provided free of charge by the Department of Industrial Relations
from its web site at
www.dir.ca.gov. These regulations are for the
convenience of the user and no representation or warranty is made that the information
is current or accurate. See full disclaimer at
https://www.dir.ca.gov/od_pub/disclaimer.html.
Subchapter 7. General Industry Safety Orders
Group 20. Flammable Liquids, Gases and Vapors
Article 141. Container and Portable Tank Storage
Return to index
New query
§5535. Storage in Inside Storage Rooms.
In every inside storage room there shall be maintained one clear aisle at least three feet wide. Containers over 30 gallons capacity storing Category 1, 2 or 3 flammable liquids shall not be stacked one upon the other. Dispensing shall be by approved pump or self-closing faucet only.
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
HISTORY
1. Amendment filed 7-16-76; effective thirtieth day thereafter (Register 76, No. 29).
2. Amendment of section and new Note filed 5-5-2014; operative 5-6-2014 pursuant to Government Code section 11343.4(b)(3) (Register 2014, No. 19).
Go Back to Article 141 Table of Contents