This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 7. General Industry Safety Orders
Group 10. Gas Systems for Welding and Cutting
Article 82. Stationary Automatic Acetylene Generators
Return to index
New query

§4811. Generator Escape or Relief Pipes.


(a) Each generating chamber shall be provided with an escape or relief pipe, installed without traps so that any condensate will drain back into the chamber.

(b) All relief pipes shall be carried to a suitable point outside the building and shall terminate in a suitable hood or bend located at least 12 feet above the ground and at least three feet from combustible construction. Each generator shall be provided with a vent pipe of Schedule 40 galvanized iron or steel, or equivalent.

(c) Generating chamber relief pipes shall not be interconnected but shall be led separately to the outside air.

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.