Fire Protection and Prevention
The employer is responsible for establishing an effective
fire prevention program and ensuring that it is followed throughout
all phases of the construction work.
1920(a)
A. Fire-fighting equipment must be:
- Freely accessible at all times.
1920(b)
- Placed in a conspicuous location
1920(c)
- Well maintained.
1920(d)
B. A water supply that is adequate to operate fire-fighting
equipment must be made available as soon as combustible materials
accumulate. 1921(a)
C. Fire extinguisher use must comply with the following:
- Fire extinguishers must be kept fully charged, inspected
monthly, and serviced annually.
1922(a)
- At least one fire extinguisher, rated not less than 2A,
must be provided at each floor.
- At least one fire extinguisher, rated not less than 2A,
must be provided adjacent to the stairway at each floor
level.
- Fire extinguishers rated not less than 2A must be provided
for each 3,000 ft. of floor area or a fraction thereof.
- Fire extinguishers must be kept within 75 ft. of the
protected area.
1922(a)
Exception: Fire extinguishers must be kept within
50 ft. of wherever more than 5 gal. of flammable or combustible
liquid or 5 lbs. of flammable gas is being used. 1922(a)
- Training in the use of fire extinguishers must be provided
annually. 6151(g)
Note: See specific SOs and manufacturing specifi
cations for appropriate use of fire
|