Electrical
Each year a large number of employees are injured or killed
because they come into contact with energized electrical wiring
or equipment. The Electrical Safety Orders (ESOs) are designed
to control or to eliminate these often deadly exposures and
include:
April 2007 Update
Construction Safety Orders - General
Section 1518(d), Protection from Electric Shock (other than excavations): Protective equipment or devices must be used to protect employees if a recognized hazard exists. Barricades must be used in lieu of other protective equipment. The employer must identify exposed or concealed energized electric power circuits if any person, machine, or tool might come into contact with the circuit. Legible markings or warning signs must indicate the presence of energized electrical circuits. Employees must be advised of the location of energized circuits, the hazards, and protective measures.
http://www.dir.ca.gov/Title8/1518.html
|
A. General requirements for low-voltage systems ( <= 600
V)
- Only qualified persons may work on electrical equipment
or systems. 2320.1(a)
- Maintenance of electrical installations is required to
ensure their safe condition. 2340.1
- Electrical equipment and wiring must be protected from
mechanical damage and environmental deterioration. 2340.26,
2340.11(a)(2),
2340.23
- Covers or barriers must be installed on boxes, fittings,
and enclosures to prevent accidental contact with live parts.
2340.17(a)
B. Main service equipment
Whenever the electric utility provides service via overhead
lines, the installation must:
- Consist of an acceptable service pole. 2405.3
- Be suitably grounded. 2395.5(b)
- Provide suitable over current protection. 2390.1
C. Wiring methods and devices
- Flexible cords may be used in place of permanent wiring
methods for temporary work if the cords are equipped with
an attachment plug and energized from an approved receptacle.
2500.7(a),(b)
- Flexible cords must be Type S and cannot be spliced unless
they are size No. 12 (or larger). 2500.9(a)
- Skirted attachment plugs must be used on all equipment
operating at more than 300 V. 2510.7(b)
D. Grounding
- Each receptacle must have a grounding contact that is
connected to an equipment grounding conductor. 2510.7(a)
- Temporary wiring must be grounded. 2405.2(g)
- Powered tools and electrical equipment with exposed,
non current-carrying metal parts must be grounded. 2395.45(b)
Exception: Double insulated powered tools need not
be grounded. 2395.45(b)
- Generators rated greater than 5,000 V or multi-phase
must be grounded. 2395.6(a)(4)
Exception: A portable or vehicle-mounted generator
need not be grounded if it is rated less than 5,000 V
and single phase, provided that the grounding terminals
of its receptacle are bonded to the vehicle frame, the
generator frame, and to the plugged-in equipment. 2395.6(a)
E. Ground-fault circuit interrupters (GFCIs)
The GFCI device senses ground faults (accidental electrical
paths to ground) in circuits and immediately cuts off all
electrical power in that circuit.
- GFCIs are required on receptacles that are not connected
to the sites permanent wiring and that have a rating
of 15 or 20 amps., 120 V, AC, single phase. 2405.4(c)
- The assured equipment grounding conductor program (AEGC
program) is an approved alternative to the GFCI requirement
if the following program elements are included: 2405.4(d)
- A description of the program must be written.
- The employer shall designate one or more qualified
persons to implement the program.
- Daily visual inspection of included equipment must
be conducted.
- The following tests shall be performed:
- All equipment grounding conductors shall be tested
for continuity and shall be electrically continuous.
- All plugs and receptacles must be tested for
proper attachment to the equipment grounding conductor.
- The tests shall be performed as follows:
- Before the first use of newly acquired equipment
- Before equipment is returned to service
- Before equipment is used after an incident that
may have caused damage
- At intervals not to exceed three months
- The employer shall not make available or permit the
use of equipment that has not met the requirements of
2405.4(d).
- A means of identifying tested equipment shall be
provided.
F. High-voltage power lines (> 600 V)
- Great care must be taken when working or operating equipment
near overhead high-voltage power lines.
- The required minimum safe distances (clearance) from
overhead lines energized by 600 V to 50,000 V are: 2946
- For boom-type equipment in transit, 6 ft.
- For boom-type equipment in operation, 10 ft.
- For people working near overhead lines, 6 ft.
Note: See 2946
for minimum required clearances from voltages greater
than 50,000 V.
- The following activities are prohibited unless overhead
power lines have been de-energized and visibly grounded:
- Work over high-voltage lines. 2946(b)(1)
- Work within required clearances. 2946(b)(2)
Note: When work is to be performed within minimum
required clearances, the power line operator must
be notified. 2948
G. High-voltage warning signs. 2947
High-voltage warning signs must be posted in plain view of
equipment operators.
H. Lock-out procedures
Lock-out procedures must be followed during the cleaning,
servicing, or adjusting of machinery. GISO 3314,
ESO 2320.4
|